Air Circuit Breaker (ACB) - BCW1 4000/3P is a circuit breaker: it opens on overload or short circuit, protecting the generator, the cabling and the downstream load.
A breaker should not trip in normal service. If it opens at the usual load, the cause is nearly always a mis-set trip, loose terminals generating heat, or a breaker sized below the real set current.
Specifications and compatibility
- Brand
- BCP
- Model
- BCW1 4000/3P (4000A)
- Type
- Drawout Circuit Breaker
- Electrical type
- Air Circuit Breaker (ACB)
- Amperage
- 4000 A
- Pole
- 3P
- Country of origin
- China
How to verify before ordering
- Match rated current, trip curve (B/C/D) and breaking capacity to the circuit it protects.
- Check whether the panel uses a moulded case, DIN rail or open-frame breaker, and how many poles.
- Confirm the kA rating: fitting one below the original leaves the panel unprotected against short circuit.
- The reference shown on this listing is BCW1 4000/3P (4000A); cross-check it against the one stamped on the removed part.
- Declared origin: China. Check this if your purchase requires a specific origin.
Frequently asked questions
Why does the breaker trip when the set starts?
The motor inrush or the transformer magnetising current crosses the instantaneous threshold. It is solved with the right curve (type D or a short-delay setting), not by raising the rating without recalculating the cable.
Can I replace it with a higher amperage one?
Not without recalculating cable and alternator. A larger breaker leaves the cable unprotected and pushes the damage into the winding.
Related parts
- Interruptor de aire inteligente BCW1 2000/3P/800A
- Fuses – High Voltage Fuses
- PORTAFUSIBLE RT18-32 4P 500/690V
- DISYUNTOR SCHNEIDER GV2-ME22C
- PORTAFUSIBLE RT18-32 1P 690V
See the spare parts catalogue or request a quotation quoting the equipment reference. Third-party trademarks are cited for identification purposes only.
Specifications
| Characteristics | |
|---|---|
| Brand | BCP |
| Country of Origin | China |
| Type | Drawout circuit breaker |
| Model | BCW1 4000/3P (4000A) |
| Control Voltage | 220 VAC |
| Pole | 3P |
| Amperage (A) | 4000 A |
| Electrical power | |
|---|---|
| Electrical | Low-voltage product category |